The SOLOnet series of digital infrared thermometers provides cost effective, reliable measurement in a wide variety of process control applications.
SOLOnet digital thermometers can be used in stand-alone, single point or multipoint installations with individually, remotely adjustable sub-temperature ranges, current outputs, emissivity or non greyness compensation and end user defined alarms settings.
Choice of built-in peak picker, track and hold or averager signal processing functions ensures accurate measurement of difficult or complex processes.
The optional DIN-rail mounted SOLOnet Webserver/Ethernet Interface Unit provides the user with a wide choice of configuration, interconnection, system monitoring and maintenance options. |
|
|
| Features |
|
|
Intelligent, digital infrared thermometers with flexible methods of configuration |
|
RS485, Web browser or Ethernet interface |
|
High precision inputs/outputs, both digital and current formats |
|
Simple and easy to configure to user requirements |
|
Field changeable optics without need to recalibrate or any additional parts |
|
Sapphire window is standard on all models - robust, low maintenance |
|
Laser alignment option |
|
Built-in peak picker, track & hold and averager time functions |
|
Choice of alarm outputs, including 'insufficient signal' alarm for ratio thermometers |
|
Rugged, sealed aluminium housing |
|
Optional water cooled and air purged mountings and accessories |
|
Two year warranty |
| |
|
|
| SOLOnet offers a choice of 4 field changeable, fixed-focus optical configurations focused at 250, 500, 1000mm or infinity. The optics are simple to change using a colour coded spacer system for ease of identification - no need for recalibration - no additional parts required. |
|

A wide choice of thermometer protection,
cooling and mounting options.
|

User configurable between four focus distances with robust sapphire protection window as standard. |
|

Optional laser targeting system, activated remotely or from the thermometer. |
| Model |
SN11 |
SN21 |
SN51 |
SNR1 |
| Operating range: |
550 to 1750°C/ 1022 to 3182°F
|
250 to 1300°C/ 482 to 2372°F
|
200 to 1100°C/ 392 to 2012°F |
700 to 1750°C/ 1292 to 3182°F |
| Specified range: |
600 to 1750°C/ 1112 to 3182°F |
300 to 1300°C/ 572 to 2372°F |
250 to 1100°C/ 482 to 2012°F |
750 to 1750°C/ 1382 to 3182°F |
| Spectral response: |
1µm |
1.6µm |
5µm |
1µm ratio |
| Field of view (95% energy): |
100:1 |
100:1 |
60:1 |
100:1 |
| Focusing: |
Fixed, user configurable focus: 250mm/9.8in, 500mm/19.7in, 1000mm/39.4in and infinity |
| Output: |
0 or 4 to 20mA user selectable (isolated 50V) |
| Response time (0 to 90%): |
10ms |
10ms |
50ms |
10ms |
| Emissivity: |
0.10 to 1.00 |
| Non greyness: |
0.80 to 1.25 |
| Resolution (mid range): |
<1K |
| Stability: |
0.2°/° |
0.2°/° |
0.02%K/K |
0.05%K/K |
| Accuracy (absolute): |
0.3%K |
2K |
0.35%K |
0.6%K |
| Time functions: |
Peak picker, track and hold, and averager |
| Alarm outputs: |
Process high, process low, internal temperature, emissivity/NG signal lost, insufficient signal (SNR1 only); rated to 50V d.c., 0.1A non-inductive, NO or NC - software selectable |
| Optional sighting: |
Laser defining optical axis; class 2, 1mW, 650nm, 120s ON duration, automatic switch-off |
| Ambient limits: |
5 to 60°C/41 to 140°F specified; 0 to 70°C/32 to 158°F operating |
| EMC: |
EN 61326:1999 (immunity and emission) |
| Sealing: |
IP65/NEMA 4X |
| Vibration: |
3g (10 to 300Hz) |
| Power supply: |
18 to 30V d.c. (24V d.c. nominal) |
| Optional accessories: |
Air cooled/purged jacket, water cooled/air purged jacket, air purge and mounting bracket, 1-axis and 2-axis adjustable mounting brackets, 3m, 15m, 25m prewired cable assemblies,
Web/Ethernet Interface Unit SN-W/E, d.c. power supply unit, temperature indicator unit LMi |
|
|
|
|